EOE-W55RP20_BACnet Module Firmware Update Guide

Firmware 1.0.0

This guide explains how to replace the firmware of a running module with a new version. There are two ways to do it, and both give the same result.

MethodUse it when
Method 1: Web interfaceThe module is on the network and the web interface is available
Method 2: AT commands (UART)The network is not available, or you update through the host MCU's AT port

Both methods first check the file and store it in a spare area, and install it at a reboot. If a transfer fails or is cut off, the firmware that is running now stays as it is. With the web interface the module reboots by itself a few seconds later; with AT commands the host chooses the moment with AT+OTAREBOOT.

While it reboots and installs (about 15 seconds), the module does not answer BACnet. On a site in operation, schedule the update in advance. After the restart the module sends an I-Am to announce that it is back. Workstations' COV subscriptions are lost in the restart, so no COV notifications arrive until a workstation subscribes again.


Update file​

Use only the .fwpkg file for an update.

FilePurpose
w55rp20_app_1.0.0.fwpkgFirmware update. This is the file used in this guide

A .fwpkg file carries the product ID, the version and a CRC. The module checks these and refuses a file made for another product or a damaged file. A file for another product that uses the same hardware (for example the SNMP module) is refused as well, because its product ID differs.


Before you start​

  • Note the current version. The first field is the firmware version, and the fourth field is the product ID.

    AT+VERSION?
    +VERSION:"1.0.0","EOE-W55RP20_BACnet","EOE-W55RP20_BACnet-0008DC123456",0x454F4502
  • Saved network settings, BACnet settings (Device instance, mode, passwords and so on), objects and stored values, BACnet/SC certificates and private key, and the web account are all kept through the update. Settings changed over AT without AT+SAVE are lost at the reboot that installs the update, so save or undo them before you start.

  • The object CSV file uploaded through the web interface is erased when an update starts. The objects in use stay as they are, but AT+BMAPRELOAD and Re-apply stored CSV on the web no longer have a file to apply. If you manage objects with a CSV file, download it with Export active mapping on the Object mapping tab of the web interface before the update, and upload it again after the update.

  • Installation happens at reboot. Do not turn the power off while it is installing.

If the power fails during installation. The module starts the installation again from the beginning at the next power-on. The new firmware stays in the spare area until the installation has finished, so a power failure does not leave the device unusable.


Method 1: Web interface​

Step 1: Turn on the web interface​

If you already use the web interface, go to step 2.

The web interface is off by default, and from the factory there is no web password, so no one can log in. Turn the web interface on from the AT port and also set a password with AT+WEBPASS. The password must be at least 8 characters. The web commands are:

AT+WEB=1                 enable the web interface
AT+WEB=0 disable
AT+WEB=1,600 enable + session timeout of 600 s (1 … 65535)
AT+WEB? → +WEB:1,600,SET

AT+WEBUSER="admin"
AT+WEBUSER? → +WEBUSER:"admin"

AT+WEBPASS="new-password" 8 … 63 bytes
AT+WEBTIMEOUT=600 1 … 65535 s
AT+WEBTIMEOUT? → +WEBTIMEOUT:600
AT+SAVE

Step 2: Log in​

In a browser, open port 50003 at the module's address.

http://192.168.11.2:50003/

192.168.11.2 is the factory default address. If you changed it, use the address that AT+IP? reports. Enter the account name (factory default admin) in User and the password from step 1 in Password, then click Sign in.

Login screen

The port is 50003, not 80. If you enter only the address, the browser goes to port 80, gets no response, and the web interface looks as if it were off.

Step 3: Upload the file​

  1. Click the Firmware tab at the top.

    Firmware tab

  2. Click the file selection button and choose w55rp20_app_1.0.0.fwpkg.

    Choosing the file

  3. Click Upload.

  4. A confirmation prompt appears. Check the file name and click OK to start the upload. Cancel uploads nothing.

    Update confirmation prompt

  5. While the file is uploading, Uploading ... do not close this page. is shown. Do not close or reload the page.

    Uploading

Step 4: Automatic restart and installation​

When the file passes its checks, a Download complete box appears in the middle of the page and counts down to the restart.

Download complete countdown box

When the countdown ends, the module reboots by itself and installs the new firmware. There is nothing else to click. The web interface does not respond in the meantime and the box shows Restarting and installing.... Do not turn the power off while it is installing.

Step 5: Check​

When the module answers again (about 15 seconds), the page reloads by itself and shows the login screen.

Login screen after the restart

Log in again and check the following on the Dashboard tab.

ItemValue
firmwareThe new version (for example 1.0.0)
ota_stateIDLE

On a workstation, the Firmware_Revision of the Device object changes to the same value.

To stop before the restart, send AT+OTACANCEL on the AT port during the countdown. The received file is discarded and the module does not restart.

If the upload is refused​

If Upload rejected (<code> <reason>) appears, the file is not installed and the module does not restart. The firmware that is running now is unchanged, so fix the cause and start again from step 3.

Upload rejected

ShownWhat to check
400 Rejected PackageMake sure it is a .fwpkg file and that it is for this module. A file for another product is refused
422 Image CRC MismatchThe file is damaged. Download the file again and upload it
422 Not An ApplicationThe file is intact but is not firmware this module can run. Make sure it is the correct .fwpkg file
409 Storage BusyAn update is running on the AT port, or a CSV file is being uploaded or re-applied. Upload again when it has finished
400 Truncated … · Transfer IncompleteThe file did not arrive in full. Upload it again
400 Overlong PayloadThe file is longer than its header says. Download the original .fwpkg again and upload it
500 Storage FailureThe module could not write the file to flash. Upload it again, and contact WIZnet if it keeps happening
Upload rejected: the connection closed before the module answered …The connection to the module was lost during the upload, and the module does not install this file. A file for another product, or a file with extra data at its end, also shows this, because the module refuses it at once (the picture above). No reply: … may show for a moment before this message appears. Make sure the .fwpkg is for this module, then reload the page and upload again, or update with method 2 (AT commands)

Method 2: AT commands (UART)​

This section uses the terminal program Tera Term as the example. Menu names are those of the English interface. With another terminal program the steps are the same: use its function that sends a file unchanged (binary transfer).

Step 1: Set up Tera Term​

In Setup → Serial port..., match the settings of the module's AT port. The values below are the factory defaults.

Setup → Serial port...Serial port setup dialog
Setup → Serial port...Serial port setup dialog
ItemValue
Speed115200
Data8 bit
Paritynone
Stop bits1 bit
Flow controlnone
Transmit delay0 msec/char, 0 msec/line

In Setup → Terminal..., set the following.

Setup → Terminal...Terminal setup dialog
Setup → Terminal...Terminal setup dialog
ItemValueWhy
New-line, TransmitCR+LFAT command lines end with CRLF
Local echoUncheckedIf it is on, the contents of the file are printed on the screen while it is sent, and the screen is garbled

Type AT and check that OK comes back. The module does not echo what you type, so the commands you type do not appear on the screen; only the responses do.

Some port settings prevent an update. With 7 data bits or XONXOFF flow control the firmware file cannot be sent intact, so the module does not start the transfer (+OTAFWUP:ERROR,PORT,"…" and ERROR:NOT_SUPPORTED). Use AT+UART to change to 8 bits and one of the flow controls NONE, RTSCTS or DTRDSR, then AT+SAVE and restart with AT+REBOOT (port settings change only at a restart), set Tera Term to the same settings, and continue.

Step 2: Start the transfer​

Enter the following command. 60 is how long the module waits for data, in seconds. Any value from 1 to 600 can be used.

AT+OTAFWUP=60
+OTAFWUP:READY

Screen showing +OTAFWUP

+OTAFWUP:READY means the module is ready to receive the file. On receiving the command the module first erases the spare area, so this line appears about 2 seconds later. Anything sent before this line loses its first part, so always wait for it.

If nothing arrives for 60 seconds after READY, the module cancels the transfer and returns to command mode. Start step 3 within that time.

Do not type anything after READY. From this point every byte that arrives is treated as firmware data. A single Enter changes the first byte of the file, and the transfer is refused.

Step 3: Send the file (binary transfer)​

  1. Click File → Send file....

  2. Choose w55rp20_app_1.0.0.fwpkg.

  3. Check the Binary option.

    File → Send file...Choosing the file and checking Binary
    File → Send file...Choosing the file and checking Binary
  4. Click Open (or OK) to start the transfer.

Always check Binary. Without it, Tera Term sends the file as text, changing the line-break characters (CR, LF) or leaving some bytes out. The file then does not arrive as it was, and the module refuses it with an error such as IMAGECRC or TIMEOUT.

Tera Term shows a progress window during the transfer. Wait until it closes. At 115200 bps this takes about 40 seconds.

Transfer progress window

Step 4: Check that the transfer completed​

When the transfer is finished, the screen shows these three lines. The first one (IMAGE) already appeared early in the transfer, right after the start of the file was received.

+OTAFWUP:IMAGE,1.0.0,408188
+OTAFWUP:DONE,408188,1.0.0
OK

Screen after the transfer completed

LineMeaning
+OTAFWUP:IMAGE,<version>,<size>The start of the file (the header) passed its checks. Appears early in the transfer
+OTAFWUP:DONE,<size>,<version>The whole file arrived, passed its checks and is stored in the spare area

After DONE and OK the file is ready. It is not installed yet. Unlike the web method, the module does not restart by itself: send AT+OTAREBOOT in step 5 to install it. You can also check the state with the following command.

AT+OTASTATUS?
+OTASTATUS:READY,408188,408188,100

Step 5: Reboot to install​

AT+OTAREBOOT
OK

The module installs the new firmware as it reboots. When the installation has finished and the module has started again, it sends a line with the new version.

+READY:"1.0.0"

Screen showing +READY after the reboot

Step 6: Check​

AT+VERSION?
+VERSION:"1.0.0","EOE-W55RP20_BACnet","EOE-W55RP20_BACnet-0008DC123456",0x454F4502

If the first field shows the new version, the update is complete.

If an error occurs​

On an error the module sends +OTAFWUP:ERROR,<reason> and ERROR:<code>, then returns to command mode. The firmware that is running now is unchanged, so fix the cause and start again from step 2.

ReasonMeaningWhat to do
MAGICNot a firmware packageMake sure you chose the .fwpkg file and did not press a key after READY
HEADERCRCThe start of the file is damagedCheck that Binary is checked, and download the file again
PRODUCTThe file is for another productMake sure the file is for this module. The two values that follow are the product IDs of the file and of the module
IMAGECRCThe received contents failed the checkCheck that Binary is checked, and download the file again
NOTAPPThe file is intact but is not firmware this module can runMake sure it is the correct .fwpkg file
TIMEOUT,<received>,<total>The file did not arrive in fullCheck that the transfer started within the time set in step 2 and that Binary is checked
TIMEOUT,<received>,<total>,OVERRUNThe PC sent everything but the module missed part of itLower the baud rate or use RTSCTS flow control
PORTThe transfer cannot run with the current port settingsCheck the port settings in step 1
BUSYAn update, or a CSV upload or re-apply, is running from the web interfaceTry again when it has finished

For other reasons, see chapter 13 of the AT Command Guide.

  • If the transfer seems to have stopped, do not press any key; wait. When the time set in step 2 has passed, the module sends TIMEOUT and returns to command mode by itself.
  • A few ERROR:INVALID_COMMAND lines may follow an error. They are the rest of the file being read as commands. Press Enter once to clear them.
  • The AT method erases the spare area when the transfer starts. If the transfer fails, an image received earlier is gone as well. The running firmware is not affected.

Good to know​

  • Once a file has been received (READY), any reboot installs the new firmware: AT+REBOOT, Reboot on the web interface, ReinitializeDevice from a workstation, or turning the power off and on.
  • After a web upload the module reboots by itself a few seconds later; after an AT transfer it waits for the host to reboot it.
  • To discard a received file without installing it, send AT+OTACANCEL before rebooting.
  • A factory reset is not possible while a received file is waiting. Install or cancel it first.
  • The start reason reported for the first start after an update (+DIAG:RESET in AT+DIAG?, and the Device's Last_Restart_Reason) is that of the reboot that led to the installation.

DocumentWhen to read it
AT Command GuideChapter 13. Details of AT+OTAFWUP and the other update commands
Getting Started GuideConnecting the module, setting the IP address, turning on the web interface